Commercial ERV heat recovery unit,
1000 m³/h

Commercial ERV heat recovery unit with 1000 m³/h airflow capacity

ZE100GUCDA0

  • Integrated energy recovery technology helps maintain balanced indoor conditions and improves ventilation efficiency
  • 1000 m³/h airflow capacity ensures a stable air supply for various types of facilities
  • Low-profile housing with a height of 365 mm simplifies ceiling installation
  • Supports ePM10 50% (M5), ePM1 70% (F7), and ePM1 80% (F9) filters, with extended filtration options available
  • The CO₂ sensor automatically adjusts ventilation intensity based on indoor air quality
  • An optional Wi-Fi module enables remote system control
  • Safe Plus insulation improves operational reliability and hygiene
  • One wired controller can manage up to 16 indoor units

TECHNICAL SPECIFICATIONS

KEY SPECIFICATIONS
Normal air flow rate (m³/h) 1000
Voltage, phase, frequency (V, ph, Hz) 220-240 V, 1 ph, 50-60 Hz
External static pressure (Pa)* 160 / 102 / 57
Air flow rate (m³/h)* 1000 / 800 / 600
Dimensions (W x H x D), (mm) 1,062 x 365 x 1,240
Weight (kg) 54,4
ENERGY RECOVERY VENTILATION (ERV) MODE
Current (A)* 3,00 / 1,90 / 1,00
Power input (W)* 475 / 280 / 140
Sound power level (dB(A))* 62 / 56 / 52
Sound pressure level (dB(A))* 40 / 36 / 29
Temperature exchange efficiency (heating / ErP), (%) 73
Enthalpy exchange efficiency (heating / JIS), (%)* 72 / 73 / 74
Enthalpy exchange efficiency (cooling / JIS), (%)* 63 / 67 / 71
DUCT WORK
Quantity / diameter 4 / Ø 250
SUPPLY AIR FAN
Quantity / type 1 / direct-drive Sirocco
EXHAUST AIR FAN
Quantity / type 1 / direct-drive Sirocco
FILTERS
Default Supply air filter class: F7
Exhaust air filter class: M5
(according to ISO 16890/EN 779)
Optional Supply air filter class: M5, F7, F9
Exhaust air filter class: M5, F7, F9

*Boost / high / low modes