м. Дніпро
+38 (099) 528 95 23
klimstar.dnepr@gmail.com

Hydrosplit-integrated water tank R32,
3-phase, 16 kW

Hydrosplit integrated water tank system, R32 refrigerant, three-phase, 16 kW

HN1616Y NB1 + HU163MRB U30

  • A fully integrated hot water tank saves space and significantly reduces installation time
  • The absence of refrigerant piping eliminates the risk of leaks, improving overall system safety and reliability
  • A high ErP energy efficiency rating of LWT A+++ / A++ (35°C / 55°C) ensures substantial energy savings
  • Water heating efficiency of up to 120% and an L (A+) profile ensure stable and efficient DHW system performance
  • Outlet water temperatures of up to 65°C and reliable operation down to -25°C broaden the system’s application range across various climates
  • Wi-Fi control (ThinQ) with smart grid and PV/ESS support enables intelligent system management and optimized energy use

TECHNICAL SPECIFICATIONS

POWER SUPPLY
Voltage, phase, frequency (V, ph, Hz) 380-415 V, 3 ph, 50 Hz
SEASONAL EFFICIENCY DATA (HEATING)
Seasonal space heating eff. class (35°C / 55°C) A+++ / A++
Seasonal space heating efficiency (ηS) (35°C / 55°C) 179 / 135
SCOP (35°C / 55°C) 4,55 / 3,45
WATER HEATING EFFICIENCY DATA
COP DHW, average climate 2,74
Declared load profile, average climate L
Water heating efficiency (ηWH), average climate 120
Water heating efficiency class, average climate A+
NOMINAL CAPACITY AND COP (A+7/W+35)
Heating capacity (kW) 16,00
COP 4,80
NOMINAL CAPACITY AND COP (A+2/W+35)
Heating capacity (kW) 13,80
COP 3,60
NOMINAL CAPACITY AND COP (A+7/W+55)
Heating capacity (kW) 12,00
COP 2,80
NOMINAL CAPACITY AND EER (A+35/W+18)
Cooling capacity (kW) 16,00
EER 4,00
NOMINAL CAPACITY AND EER (A+35/W+7)
Cooling capacity (kW) 16,00
EER 2,50
OPERATION RANGE (OUTDOOR AIR TEMPERATURE)
Heating & DHW (min. ∼ max.), °C -25 ∼ 35
Cooling (min. ∼ max.), °C 5 ∼ 48
OPERATION RANGE (LEAVING WATER TEMPERATURE)
Heating (min. ∼ max.), °C 15 ∼ 65
Cooling (min. ∼ max.), °C 5 ∼ 27
DHW (min. ∼ max.), °C 15 ∼ 80
REFRIGERANT
Type R32
GWP 675
Precharged amount (g) 2,100
PIPING CONNECTIONS (WATER CIRCUIT/OUTDOOR UNIT)
Inlet diameter (inch) Male PT 1″
Outlet diameter (inch) Male PT 1″
PIPING CONNECTIONS (WATER CIRCUIT/INDOOR UNIT)
Inlet/outlet diameter for space heating (inch) Female G1″
Inlet/outlet diameter for DWH (inch) Female G3/4″
Inlet/outlet diameter for ODU connection (inch) Female G1″
Recirculation (inch) Female G3/4″
SOUND POWER LEVEL (OUTDOOR UNIT)
Rated / low noise mode (dB(A)) 63 / 60
SOUND POWER LEVEL (INDOOR UNIT)
Rated (dB(A)) 43
SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)
Rated / low noise mode (dB(A)) 41 / 38
SOUND PRESSURE LEVEL AT 1M (INDOOR UNIT, CONVERT USING SWL)
Rated (dB(A)) 35
DIMENSIONS
Outdoor unit (WхHхD), (mm) 950 х 1,380 х 330
Indoor unit (WхHхD), (mm) 601 x 1,812 x 685
WEIGHT
Outdoor unit (empty), (kg) 91,7
Indoor unit (empty), (kg) 130,0
EXTERIOR
Outdoor unit (color / RAL code) Warm gray / RAL 7044
Indoor unit (color / RAL code) White / RAL 9002