м. Дніпро
+38 (099) 528 95 23
klimstar.dnepr@gmail.com

Monobloc with hydro unit R290,
1-phase, 16 kW

Monobloc Heat Pump with hydro unit, R290, 1-Phase, 16 kW

HN1616HC NK0 + HM161HF UB60

  • The unit uses the eco-friendly R290 refrigerant, known for its exceptionally low global warming potential of only 3
  • Thanks to its innovative construction, no refrigerant pipework is required, reducing installation complexity and saving time on setup
  • The unit meets the high ErP LWT energy efficiency rating of A+++ / A+++ at water temperatures of 35°C and 55°C
  • The elegant gray casing blends seamlessly with modern architecture and a wide range of building facades
  • The system is capable of producing water temperatures up to 75°C while maintaining stable performance in outdoor conditions down to -28°C
  • Designed for quiet operation, the 16 kW model generates just 52 dB(A), ensuring a comfortable environment for residential use

TECHNICAL SPECIFICATIONS

POWER SUPPLY
Voltage, phase, frequency for outdoor unit (V, ph, Hz)220-240 V, 1 ph, 50 Hz
Voltage, phase, frequency for indoor unit (V, ph, Hz)220-240 V, 1 ph, 50 Hz
SEASONAL EFFICIENCY DATA (HEATING)
Seasonal space heating eff. class (35°C / 55°C)A+++ / A+++
Seasonal space heating efficiency (ηS) (35°C / 55°C)201 / 154
SCOP (35°C / 55°C)5,11 / 3,92
NOMINAL CAPACITY AND COP (A-7/W+35)
Heating capacity (kW)13,80
COP3,17
NOMINAL CAPACITY AND COP (A-7/W+55)
Heating capacity (kW)10,90
COP2,26
NOMINAL CAPACITY AND COP (A+7/W+35)
Heating capacity (kW)16,00
COP4,30
NOMINAL CAPACITY AND COP (A+2/W+35)
Heating capacity (kW)14,50
COP3,49
NOMINAL CAPACITY AND COP (A+7/W+55)
Heating capacity (kW)12,00
COP3,30
NOMINAL CAPACITY AND EER (A+35/W+18)
Cooling capacity (kW)12,50
EER3,70
NOMINAL CAPACITY AND EER (A+35/W+7)
Cooling capacity (kW)12,50
EER2,95
OPERATION RANGE (OUTDOOR AIR TEMPERATURE)
Heating & DHW (min. ∼ max.), °C-28 ∼ 35
Cooling (min. ∼ max.), °C5 ∼ 48
OPERATION RANGE (LEAVING WATER TEMPERATURE)
Heating (min. ∼ max.), °C15 ∼ 75
Cooling (min. ∼ max.), °C5 ∼ 27
DHW (min. ∼ max.), °C15 ∼ 80
REFRIGERANT
TypeR290
GWP3
Precharged amount (g)1,200
PIPING CONNECTIONS (WATER CIRCUIT/OUTDOOR UNIT)
Inlet diameter (inch)Male PT 1″
Outlet diameter (inch)Male PT 1″
PIPING CONNECTIONS (WATER CIRCUIT/INDOOR UNIT)
Inlet/outlet diameter for space heating (inch)Male PT 1″
Inlet/outlet diameter for ODU connection (inch)Male PT 1″
SOUND POWER LEVEL (OUTDOOR UNIT)
Rated / low noise mode (dB(A))52 / 51
SOUND POWER LEVEL (INDOOR UNIT)
Rated (dB(A))39
SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)
Rated / low noise mode (dB(A))30 / 29
SOUND PRESSURE LEVEL AT 1M (INDOOR UNIT, CONVERT USING SWL)
Rated (dB(A))31
DIMENSIONS
Outdoor unit (WхHхD), (mm)1,560 х 1,019 х 520
Indoor unit (WхHхD), (mm)490 x 850 x 315
WEIGHT
Outdoor unit (empty), (kg)181,0
Indoor unit (empty), (kg)30,0
EXTERIOR
Color of outdoor unit chassis (color / RAL code)Dawn gray / RAL 7037
Color of outdoor unit front grille (color / RAL code)Dark dawn gray / RAL 7012
Indoor unit (color / RAL code)Noble white / RAL 9016