м. Дніпро
+38 (099) 528 95 23
klimstar.dnepr@gmail.com

Split hydro box R410A, 1-phase, 16 kW

R410A split hydro box heat pump for heating, 16 kW, single-phase

HN1616M NK5 + HU161MA U33

  • Designed for facilities with high thermal loads, ensuring efficient operation even in cold climate conditions
  • Reliable performance of the hydronic system with simplified installation and wiring, thanks to the integrated hydro unit in the indoor module
  • Flexible design and installation of refrigerant piping for various system configurations
  • High energy efficiency in accordance with the ErP standard: class A+++ / A++ (at 35°C / 55°C)
  • Leaving water temperature up to 57°C and stable operation at ambient temperatures down to -25°C
  • Advanced control capabilities, including Wi-Fi (ThinQ), Smart Grid integration, and compatibility with solar (PV) and energy storage systems (ESS)

TECHNICAL SPECIFICATIONS

POWER SUPPLY
Voltage, phase, frequency (V, ph, Hz) 220-240 V, 1 ph, 50 Hz
SEASONAL EFFICIENCY DATA (HEATING)
Seasonal space heating eff. class (35°C / 55°C) A+++/A++
Seasonal space heating efficiency (ηS) (35°C / 55°C) 179 / 130
SCOP (35°C / 55°C) 4,56 / 3,32
NOMINAL CAPACITY AND COP (A+7/W+35)
Heating capacity (kW) 16,00
COP 4,26
NOMINAL CAPACITY AND COP (A+2/W+35)
Heating capacity (kW) 13,80
COP 3,60
NOMINAL CAPACITY AND COP (A+7/W+55)
Heating capacity (kW) 12,00
COP 2,55
NOMINAL CAPACITY AND EER (A+35/W+18)
Cooling capacity (kW) 13,00
EER 3,61
NOMINAL CAPACITY AND EER (A+35/W+7)
Cooling capacity (kW) 8,92
EER 3,53
OPERATION RANGE (OUTDOOR AIR TEMPERATURE)
Heating & DHW (min. ∼ max.), °C -25 ∼ 35
Cooling (min. ∼ max.), °C 5 ∼ 48
OPERATION RANGE (LEAVING WATER TEMPERATURE)
Heating (min. ∼ max.), °C 15 ∼ 57
Cooling (min. ∼ max.), °C 5 ∼ 27
DHW (min. ∼ max.), °C 15 ∼ 80
REFRIGERANT
Type R410A
GWP 2,088
Precharged amount (g) 2,500
PIPING CONNECTIONS (OUTDOOR UNIT/REFRIGERANT CIRCUIT)
Gas (mm (inch)) Ø 15,88 (5/8)
Liquid (mm (inch)) Ø 9,52 (3/8)
Length standard / max. (m) 7,5 / 30
Level difference max. (m) 30
Max. length without additional charge (m) 7,5
Additional refrigerant charge (g/m) 40
PIPING CONNECTIONS (WATER CIRCUIT/INDOOR UNIT)
Inlet diameter for space heating (inch) Male PT 1″
Outlet diameter for space heating (inch) Male PT 1″
SOUND POWER LEVEL (OUTDOOR UNIT)
Rated / low noise mode (dB(A)) 65 / 63
SOUND POWER LEVEL (INDOOR UNIT)
Rated (dB(A)) 44
SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)
Rated / low noise mode (dB(A)) 43 / 41
SOUND PRESSURE LEVEL AT 1M (INDOOR UNIT, CONVERT USING SWL)
Rated (dB(A)) 36
DIMENSIONS
Outdoor unit (WхHхD), (mm) 950 х 1,380 х 330
Indoor unit (WхHхD), (mm) 490 х 850 х 315
WEIGHT
Outdoor unit (empty), (kg) 84,8
Indoor unit (empty), (kg) 40,5
EXTERIOR
Outdoor unit (color / RAL code) Warm gray / RAL 7044
Indoor unit (color / RAL code) Noble white / RAL 9016